Power Factor Formula (3-phase):
From: | To: |
Definition: Power factor is the ratio of real power (watts) to apparent power (volt-amps) in an AC electrical system.
Purpose: It measures how effectively electrical power is converted into useful work output by a motor.
The calculator uses the formula for 3-phase systems:
Where:
Explanation: The formula calculates the ratio between the actual power being used (watts) and the apparent power being drawn from the supply (volt-amps).
Details: A higher power factor (closer to 1) indicates more efficient power usage, reduces energy losses, and may lower electricity costs.
Tips: Enter the motor's real power in watts, line voltage (default 480V for industrial motors), and current in amps. All values must be > 0.
Q1: What is a good power factor for motors?
A: Most motors have a power factor between 0.85-0.95 at full load. Below 0.85 may indicate inefficiency.
Q2: Why is √3 used in 3-phase calculations?
A: The √3 factor accounts for the phase difference in three-phase systems (120° between phases).
Q3: How can I improve motor power factor?
A: Use power factor correction capacitors, avoid motor oversizing, and ensure proper maintenance.
Q4: Does power factor change with load?
A: Yes, power factor is typically lowest at no load and improves as the motor approaches full load.
Q5: What's the difference between leading and lagging PF?
A: Lagging PF (common for motors) means current lags voltage. Leading PF (capacitors) means current leads voltage.